My checklist for commissioning a VFD
The parameters I check before and after running a variable frequency drive for the first time, and the most common mistakes.
A variable frequency drive (VFD) soft-starts a motor, controls its speed and saves energy. With the wrong parameters, though, the motor overheats, the drive keeps tripping, or the mechanics get damaged. This is the order I follow when commissioning a drive:
Before powering up
- Nameplate data: Note the motor's voltage, current, frequency, speed and power.
- Connection: Should the motor be wired star or delta? It must match the drive's output voltage.
- Cabling: Use shielded cable between drive and motor and ground the shield properly at both ends. Very long motor cables may need an output filter.
- Input protection: Input fuses or breakers should match the values in the drive manual.
Core parameters
- Motor data: Enter the nameplate values into the drive.
- Auto-tune: If possible, decouple the motor and run a full auto-tune; otherwise use the static tune. Vector control depends on it.
- Control source: Where do start/stop and the speed reference come from? Keypad, terminals or communication (Modbus etc.).
- Min/max frequency: Very low speeds can hurt cooling on pumps and fans. Don't exceed the maximum speed the mechanics can handle.
- Ramp times: Too short an acceleration time causes overcurrent trips; too short a deceleration time causes overvoltage trips. High-inertia loads may need a braking resistor.
- Motor overload protection: Set thermal protection to the motor's rated current.
First run
- Run at a low frequency (e.g. 5–10 Hz) and check the direction of rotation. If it's wrong, swap two output phases or use the direction parameter.
- Watch the current. Unexpectedly high current at no load points to a wiring or parameter error.
- Increase speed gradually and listen for vibration and noise.
Common faults
| Fault | Likely cause |
|---|---|
| Overcurrent while accelerating | Ramp too short, jammed load, wrong motor data |
| Overvoltage while decelerating | Decel ramp too short, no braking resistor |
| Motor overheating | Long periods at low speed, wrong thermal setting |
| Noise on measurements/communication | Missing shielding and grounding, cables bundled together |
Last step: back up
When commissioning is done, back up the parameters and add them to the project files. If the drive is ever replaced, you can restore the same settings in minutes.